Building a Legionella water management plan that holds up
IRIS microbiology team · CDC ELITE, ISO 11731 · 18:05
ASHRAE 188 in plain terms: where to sample, how often, and what to do with a positive result before it becomes a notifiable event.
Sign in to save your place and download the material.
A water management plan (WMP) needs testing to prove it works. Testing is the measurable control step that shows the plan is doing its job and satisfies auditors.
Which rules apply
- ASHRAE 188: a WMP is required for buildings meeting population risk criteria. It sets no numeric limit. It is a process standard, so you write the control limits into your own WMP. It covers cooling towers, hot water systems, ornamental fountains and ice machines.
- CMS QSO-17-30: all Medicare and Medicaid healthcare facilities must have a WMP, and it must include routine Legionella environmental monitoring.
- NYC Local Law 77: all cooling towers must register, test and report to NYC DEP. Testing must be Legionella culture by an ELAP-certified laboratory. Legiolert does not substitute.
Where to sample
Any water system between 68 and 122°F can harbour Legionella. Focus on:
- cooling towers, the most common outbreak source
- hot water storage tanks, recirculating loops, dead legs and infrequently used outlets
- decorative fountains, whirlpool spas, hospital water systems and ice machines
Choosing the method for each round
| Situation | Method |
|---|---|
| Cooling tower in New York State or NYC | Culture (ISO 11731) |
| Healthcare facility under CMS | Culture, with Legiolert for routine checks between culture rounds |
| Potable or hot water, no rule naming culture | IDEXX Legiolert, against the control limits in your WMP |
| New building or system start-up | Culture where a rule names it, otherwise Legiolert |
| Outbreak investigation | Culture with serogroup typing |
Cooling tower response thresholds
Under 10 NYCRR Part 4, review and disinfect at or above 20 CFU/mL, and notify the health department above 1,000 CFU/mL.
What you get back
Reports give CFU/mL (culture) or MPN/100 mL (Legiolert), compared with the applicable thresholds or your WMP control limits, with corrective-action trigger language in a WMP record format. Sample on the schedule your WMP sets.
Chain of custody
Pick the form that matches your test.
Start this COCDownloads